Mixed-Mode Ventilation in the Tropics Works Better Than We Thought, If You Add a Fan

Natural ventilation is usually written off in hot-humid climates: open a window in Singapore or Mumbai and conventional wisdom says you'll just let in more heat and moisture. Our new paper in Energy and Buildings shows that conventional wisdom is too pessimistic, because it ignores the cooling effect of air movement from fans.

With Kazuki Horikoshi and Adrian Chong (National University of Singapore), we ran annual building energy simulations for a standardized apartment building across 20 tropical cities, testing automated window control against six outdoor "switch-over" temperatures and six levels of fan-generated air speed (up to 2.0 m/s), with thermal comfort assessed across 66 combinations of clothing and activity level.

The GEAR: Kajima Lab in Singapore, a naturally ventilated building with open-air corridors and ceiling fans
The GEAR: Kajima Lab, Singapore

Key Findings​

  • Elevated air movement expands where natural ventilation works: cities previously classified as having near-zero natural ventilation potential in hot-humid conditions become viable once fan-induced air speed is accounted for.
  • An outdoor switch-over temperature around 29°C is optimal for most tropical cities: windows should open below this threshold and close above it, balancing comfort gains against the risk of letting in hot air.
  • Some cities tolerate higher thresholds (up to 31°C): Bengaluru, Hyderabad, and Rio de Janeiro can push the switch-over point higher because their hot hours are often low-humidity ("low-enthalpy"), so the same temperature feels less of a burden indoors.
  • Singapore case study: at its optimal 29°C switch-over point, naturally ventilated rooms stayed comfortable for 73.3% of natural-ventilation hours (1,828 of 2,494 waking hours), across the 66 personal-factor combinations tested.
  • The fan speed you need changes through the day: required air speed rises as outdoor temperature climbs toward midday/afternoon, meaning a fixed fan setting under-delivers at the hottest times. Dynamic, variable-speed fan control performs better than a single fixed speed.

Practical Recommendations​

  • Don't rule out natural or mixed-mode ventilation in hot-humid climates based on temperature alone, factor in fan-assisted air movement before dismissing it.
  • Set window/vent control logic around a switch-over outdoor temperature near 29°C as a starting point, and tune it higher in climates with pronounced dry hot periods.
  • Pair automated natural ventilation control with variable-speed fans rather than a single fixed speed, since the air speed needed for comfort shifts across the day.
  • Consider humidity (enthalpy), not just dry-bulb temperature, when deciding switch-over thresholds, since two cities at the same temperature can have very different comfort outcomes depending on moisture content.

Mixed-mode ventilation with fans is a more powerful, more widely applicable energy-saving strategy for tropical buildings than earlier assessments suggested.

Read the full article:​

Horikoshi, K., Tartarini, F., & Chong, A. (2026). Reassessing mixed-mode ventilation in tropical climates with elevated air movement. Energy and Buildings, 372, 118311.